Product History
Rel. | Ver. | Date | IPI | Upgrade Kit | New Features | Problems Resolved |
EK | 10.75 | Oct-09 | GFK-1512S | 44A747145-G09 | NA | See GFK-1512S |
DK | 10.74 | May-08 | GFK-1512R | 44A747145-G08 | NA | See GFK-1512R |
DJ |
10.74 | Jan-08 | GFK-1512P | 44A747145-G08 | NA | Loss/add of module faults with IC693ALG222/223 |
DH | 10.73 | Mar-06 | GFK-1512N | 44A747145-G07 | NA | MOVE_REAL operation Config Not Equal with DSM324 PID Function Block |
DG | 10.60 | ATEX certification | ||||
CG | 10.60 | Jun-02 | GFK-1512m | 44A747145-G06 | NA | CPU won't handle 11K byte smart module init file Load of large (>32K) DSM zip files fails |
CF | 10.50 |
Apr-01 Oct-00 |
GFK-1512k GFK-1512j | 44A747145-G05 | NA |
Rotate Right and Rotate Left functions do not handle error condition correctly Time of Day clock at powerup may not operate Error when run-mode storing, loading, or verifying exactly 50 blocks in run mode Fatal Fault retry does not work correctly for some faults |
CE | 10.00 | Sep-00Feb-00 | GFK-1512hGFK-1512g | N/A | Hardware Update to Enhance EMC Performance | |
BE | 10.00 | Dec-99 | GFK-1512f |
44A747145-G04 |
IC693DSM314 support added Local Logic Programs with VersaPro 1.10 Reboot after Fatal Fault Drum Sequencer function |
User Flash Write and Erase Failure PLC can Automatically go to Run Mode Retentive Contact Previous Values Table not being cleared |
BD | 9.10 | Jul-99 | GFK-1512e | 44A747145-G03 | NA |
AI & AQ Above Default Values Load File of Size 1528 Bytes C Program with Code Area Greater Than 64K Bytes |
BC | 9.01 | Jan-99 | GFK-1512d | 44A747145-G02 | NA |
SNP Master mode on CPU Ports Online Changes to Reference Tables 350 9.00 Upgrade Read from Flash |
BB | 9.00 | Oct-98 | GFK-1512c |
Software Floating Point Sequential Event Recorder |
Keyswitch Configured as RUN/STOP Switch Storing IC693CMM321 Configuration with Windows PLC Programming Software RET_PBLOCK_LIST Service Request #7 | |
BA | 8.10 | May-98 | GFK-1512b | Demko Agency approval | Hardware Change that Improves Reliability |