Driver | Supported Device | Requirements | Package | Win32 | Win64 | Linux/.NET Core | Help On-Line |
Allen-Bradley Rockwell - Ethernet/IP | PLC-5, SLC-500, Micro800, MicroLogix, ControlLogix, CompactLogix and FlexLogix | - | Basic |
x
| x | x |
|
B&R - PVI | B&R devices that implement the communication protocol INA2000 | This driver requires the installation of the B&R PVI libraries. | Automation | x | x | |
|
BACnet/IP | Devices that support the BACnet/IP protocol | - | Facilities | x | x | x |
|
Beckhoff - ADS TwinCAT | Beckhoff TwinCAT systems | The Beckhoff TwinCAT Automation Device Specification (ADS) communication library, available online from Beckhoff, must be installed. | Automation | x | x | |  |
Codesys -3S | CODESYS systems | It is not necessary to install any additional/external software in order to communicate with the device. However, in cases where the Connection Type is set to "GATEWAY", the CODESYS Gateway is included in the "CODESYS Development System V3" available from the CODESYS Store. | Automation | | x | |  |
Demo | - | - | Basic | x | x | x |  |
Energy Manager RMS621 | Endress+Hauser Energy Manager RMS621 | - | Facilities | x | x | |  |
Fanuc CNC | Device 30iB, 31iB, 35iB, 0iB | Some external packages needs to be installed on the system. See the on-line help for more information. | Automation | x | | |  |
Fatek | All Fatek Plcs supporting FATEK Communication Protocol on TCP. | - | Automation | x | x | x |  |
Emerson SRTP | Emerson PACSystem RX3i PLC and GE 90-30 Series PLC | - | Basic | x | x | x |  |
Hilscher - CifX FieldBus Multi-Protocol | Devices that support one of the following protocols: AS-Interface CAN open CC-Link CompoNet DeviceNet EtherCAT POWERLINK PROFIBUS-DP PROFINET IO RT | SyCon (Hilscher's system configuration software). An Hilscher interface Card properly configured. | Automation | x | x | |  |
IEC 60870-5-104 TCP/IP | All devices supporting the communication protocol IEC 60870-5-104 as controlled station. | | Telemetry | x |
x
| x |  |
IEC 61850 MMS Client | IEC 61850 MMS servers | | Telemetry | x | x | x |  |
IoT ProgeaCloud Databoom | - | An Internet connection | IoT | x | x | x |  |
IoT PubNub | This driver connects to the PubNub Data Stream Network (DSN) | An external DLL (PubNub-Messaging.dll) not included in the standard installation package. | IoT | x | x | |  |
Konnex - KNX Eibus | Konnex - KNX Eibus KNX devices, such as light switches, dimmers, access control devices, temperature controllers and many other building automation devices. | According to the chosen communication channel, the driver requires a specific interface to connect the supervision PC with the KNX devices. | Facilities | x | x | x |  |
Lacroix Sofrel - LACBUS-PC | This driver supports all Lacroix-Sofrel devices that implement the Lacbus RTU and Softbus PL communication protocols by means of connecting with FR 1000. | - | Telemetry | x | x | |  |
Mitsubishi - Melsec FX | Mitsubishi MELSEC-FX, FX1N, FX2N, FX3U PLCs or any other compatible device. | - | Automation | x | x | x |  |
Mitsubishi - Melsec FX TCP | Mitsubishi FX3U PLCs or any compatible device. | The FX3u-ENET module needs to be configured with the FX Configurator-EN software tool supplied by Mitsubishi. | Automation | x | x | x |  |
Mitsubishi - Melsec Q TCP | Mitsubishi iQ-r and Q PLCs or any compatible device. Melsec TCP for Q series protocol. | The QJ71E71 module can be configured, using the "GX IEC Developer" or "GX Developer" software tool supplied by Mitsubishi. | Automation | x | x | x |  |
Modbus Serial RTU | All devices communicating with standard Modbus (RTU or ASCII) serial protocol as slave. | - | Basic | x | x | x |  |
Modbus TCP-IP Slave | All communication devices that implement standard MODBUS TCP protocol as master. | - | Basic | x | x | x |  |
Modbus TCP-IP Master | All devices communicating with standard Modbus TCP protocol as slave | - | Basic | x | x | x |  |
MQTT Client | This driver connects to an MQTT broker | - | IoT | x | x | x |  |
MTConnect | Devices supporting MTConnect protocol. | - | Automation | x | x | x |  |
Omron - Ethernet/IP | This driver can be used to communicate with Omron NJ/NX PLC Series and other devices that support. CIP on Ethernet/IP | - | Basic | x | x | x |  |
Omron - FINS Ethernet | CS1 PLCs CV series C200HX/C200HG/C200HE PLCs CP/CPM2x PLCs CJ1M/CJ2M/CJ2H PLCs | - | Basic | x | x | x |  |
OPC UA Client | This driver allows another server to be connected to the Movicon OPC UA server | - | Basic | x | x | x |  |
Panasonic FP MEWTOCOL | Panasonic FP series PLCs. | The Panasonic FP Driver supports also the communication via the USB port of the PLC. In this case, the software "Panasonic Electric Works PLC Virtual UART" needs to be installed. | Automation | x | x | x |  |
Phoenix Contact PLCI | ILC 1x1 Series AXC 1xxx Series (FW.version 1.x, 2.x) AXC 3xxx Series PC WORX RT BASIC/SRT | List of external packages needed to install: -Microsoft Visual C++ 2013 Redistributable x86/x64. -Microsoft .NET Framework 4.7 Developer Pack | Basic | x | | |  |
Saia DATA Mode | All Saia® PCD PLCs, provided that they support S-BUS (Data Mode) protocol on the supported communication media; i.e. RS232/RS485 (S-BUS), Ethernet (SOCKET). | - | Automation | x | x | x |  |
Siemens PC Adapter-MPI | Siemens S7-300 Series Siemens S7-400 Series VIPA 200V Series VIPA 300V Series VIPA 300S Series VIPA 500S Series | The usage of a S7 MPI serial port adapter is required, like model 6ES7-972-0CA21-0XA0. | Basic | x | x | x |  |
Siemens PPI | This driver allows you to connect Siemens S7-200 devices | Siemens S7 PPI serial port adapter | Basic | x | x | x |  |
Siemens S7 TCP | Siemens S7-300 Series via CP 343 Siemens S7-400 Series via CP 443 Siemens S7-1200 Series Siemens S7-1500 Series VIPA 200V Series with Ethernet card VIPA 300V Series with Ethernet card VIPA 300S Series with Ethernet card VIPA 500S Series with Ethernet card | - | Basic |
x
| x | x |  |
Siemens S7 TIA Portal | Simatic-S7-1200-1500 | - | Basic | x | x | |  |
Siemens Simotion | Siemens Simotion D control units. | For exchanging data with devices, this driver requires a “.sti” file exported from Siemens Scout tool. | Automation | x |
x
| |  |
SNMP Manager | Network devices that support the SNMP protocol as agent | - | Facilities |
x
| x |
x
|  |
SQL Driver | This driver provides connection to database servers | - | Basic | x | x | x |  |