Error 10060 when trying to set temp IP address for RX3i CPE305 or CPE310 ka21t0000008W8YAAU | Emerson Customer Center

Error 10060 when trying to set temp IP address for RX3i CPE305 or CPE310

Description:

Error 10060 occurs when trying to set temp IP address for RX3i CPE305 or CPE310 embedded Ethernet port.






Resolution:

The RX3i CPE305 and CPE310 embedded ethernet port does not support BOOTP or SetIP tool in Machine Edition.

This is a documented operational note as per the IPI for each product:
For the CPE305, refer to GFK-2714Y , page 14.
For the CPE310, refer GFK-2713X, page 15.


These controllers have a default IP address of 192.168.0.100.

If you cannot connect using the default IP address, use one of the following methods to initially assign an IP address:

1. Download a CPE configuration from the Programmer using a serial connection.

OR

2. Download a CPE configuration from the Programmer using the Ethernet connection
of an ETM001 in the same rack with a known IP address configuration